Twin-core PV cable (Austrian)

Twin-core solar cables are ideal for photovoltaic (PV) systems. By integrating the positive and negative conductors into a single cable, they simplify cable routing, reduce installation time and labor costs, and improve overall installation efficiency. This makes them a popular solution for utility-scale solar projects in Australia.
Send Inquiry
Product Detail

1. Application

Twin-core solar cables are ideal for photovoltaic (PV) systems. By integrating the positive and negative conductors into a single cable, they simplify cable routing, reduce installation time and labor costs, and improve overall installation efficiency. This makes them a popular solution for utility-scale solar projects in Australia.

2. Cable Construction and Identification

Item

Specification

Conductor

Soft stranded tinned copper conductor, Class 5

Insulation

XLPE; colors: red and black

Outer sheath

XLPE; color: black

Marking

EN 50618 H1Z2Z2-K 2 × **mm² DO NOT DISCONNECT UNDER LOAD Suzhou Jinhan  CO., LTD.

Reference standard / declaration

EN 50618; RoHS

3. Electrical and Operating Characteristics

Item

Specification

Ambient temperature when cable is used

90°C

Maximum rated conductor temperature

120°C (for a maximum of 20,000 hours)

Rated voltage

DC 1.5 kV

Minimum bending radius

5 × D

AC dielectric test

6.5 kV / 5 min; no breakdown

DC dielectric test

15 kV / 5 min; no breakdown

4. Table 1 — Key Technical Parameters

Size (mm²)

Conductor construction

Reference conductor diameter (mm)

Max. DC resistance at 20°C (Ω/km)

Insulation nominal thickness (mm)

Insulation minimum thickness (mm)

Sheath nominal thickness (mm)

Sheath minimum thickness (mm)

Reference cable O.D. (mm)

Min. insulation resistance at 20°C (MΩ·km)

Min. insulation resistance at 90°C (MΩ·km)

2 × 2.5

49/0.25

2.0

8.21

0.7

0.53

0.8

0.58

5.1 × 10.2

690

0.69

2 × 4

56/0.285

2.5

5.09

0.7

0.53

0.8

0.58

5.7 × 11.4

580

0.58

2 × 6

84/0.285

3.0

3.39

0.7

0.53

0.8

0.58

6.2 × 12.4

500

0.50

5. Current-Carrying Capacity — Reference Table A.3

Nominal cross-section (mm²)

Single cable free in air (A)

Single cable on a surface (A)

Two loaded cables touching on a surface (A)

1.5

30

29

24

2.5

41

39

33

4

55

52

44

6

70

67

57

10

98

93

79

16

132

125

107

25

176

167

142

35

218

207

176

6. Current Rating Conversion Factors

Ambient temperature (°C)

Conversion factor

Up to 60

1.00

70

0.92

80

0.84

90

0.75